June 24, 2003 -40- 003-2203.7 <br />Poly-Flex cut 1-inch wide samples (coupons) from each trial seam and tested the coupons with a field <br />tensiometer. Poly-Flex tested each double wedge fusion trial seam twice for peel adhesion (peel) and <br />once for bonded seam strength (shear). Poly-Flex conducted peel tests on fusion welds on both the <br />inner and outer Vacks of each peel coupon. Poly-Flex tested each extrusion trial seam twice for peel <br />and once for sheaz. <br />Golder personnel observed the testing of trial seam samples and documented test results. Golder <br />observed the tensile testing of each trial seam coupon to verify that project yield strengths were met <br />during shear testing and that failure did not occur in the weld during peel testing. When Vial seams <br />did not meet specifcations, Golder verified that the welding apparatus was not used until two <br />consecutive Vial seams performed by the same technician apparatus combination met specifications. <br />The Vial seam test results for extrusion and fusion seaming are presented in Appendix K-2 and L-2 <br />for the lower and upper geomembranes, respectively. Poly-Flex used two tensiometers during the <br />project. Tensiometer certifications are presented in Appendix N. Figures 3 and 4 show the codes <br />used to designate passing and failing test results. <br />• 6.1.3.2 Seaming Observations <br />Golder personnel observed seams before, during and after welding. Golder checked each seam for <br />adequate overlap prior to seaming and to verify that the seam area was clean and dry. <br />Golder documented Poly-Flex personnel performing the seaming and the seaming equipment used. <br />Following the completion of seaming and routine repairs, Golder checked the full length of each seam <br />to verify that no additional repairs were required. In the event that additional repairs were needed, <br />Golder marked the location requiring repair on the geomembrane, documented the location, and <br />brought the repair area to the attention of Poly-Flex. Once Poly-Flex made repairs, Golder checked <br />the repair location to verify completion. Golder inspected all seams for quality and completion. <br />Golder personnel conducted a final walk-through to verify completion of the entire geomembrane <br />system and to identify any additional damage that may have occurred during construction operations. <br />Golder recorded observations made during seaming. For the lower geomembrane layer, the <br />fusion-welding summary is presented in Appendix K-3, and the extrusion-welding summary is <br />presented in Appendix K-4. For the upper geomembrane layer, the fusion-welding summary is <br />presented in Appendix L-3, and the extrusion-welding summary is presented in Appendix L-4. <br />1:~po~l2oAa00~PmCenPSSA06m~opllzos.app.p13I3Rep.aa Golder Associates <br />