Laserfiche WebLink
Animas -La Plata Project <br />Feb 13, 2013 Draft Transfer Inspection Report <br />_ TRANSFER ISSUE I STIPULATION <br />Pump condition I See Section 5 above. <br />9. Unit Cooling Water System <br />The unit cooling water system provides cooling water for the main pump motor air cooler <br />heat exchangers. The water for the unit cooling water system is supplied from the plant's <br />suction river side raw water supply. From the suction manifold the water goes through the <br />automatic, motor - operated, self - cleaning strainers which strains the water for particles <br />greater than 1/32 ". A total of eight individual cooling water pumps are used to supply <br />cooling water to the eight main pumping unit motors. The cooling water pumps are <br />furnished in three sizes for the various pumping units. <br />TRANSFER ISSUE <br />STIPULATION <br />Drawings reflect the original <br />Reclamation will provide one spare cooling water pump for each <br />There is no spare pump <br />of the three different sized pumping units. <br />10. Mechanical Seal Water Supply Filtration System <br />The mechanical seal water supply system consists of two mechanical seal water supply <br />pumping units and two self - cleaning filters which supply filtered water to the mechanical <br />shaft seal of each main pumping unit. <br />TRANSFER ISSUE <br />STIPULATION <br />Drawings reflect the original <br />Reclamation will provide as -built drawings of the modified <br />pumps and filters <br />system. <br />There are no spare parts for <br />Reclamation will provide spare parts for the new system in <br />the modified system <br />accordance with the original specifications. <br />Background: Reclamation has previously re- engineered the mechanical seal water supply <br />system to handle higher than originally anticipated sediment loading. <br />11. Piping and Valves for Filling Discharge Line (s) <br />The designations for these valves are: <br />• Discharge, 16" pressure sustaining automatic valve (PSV) <br />• Unit 1 isolation, 16" motor - operated butterfly valve (MPE) <br />• Unit 2 isolation, 16" motor - operated butterfly valve (MPF) <br />• Durango manifold isolation, 16" motor - operated butterfly valve (MPC) <br />• City of Durango Manifold Isolation, 16" motor - operated butterfly valve (MPD) <br />TRANSFER ISSUE I STIPULATION <br />Butterfly valves condition I See Section 4 above. (MPC through MPF) <br />Background: SCADA will be modified to allow remote operation of these valves during <br />pumping to Lake Nighthorse or the COD's terminal reservoir. The operation of these valves <br />during the filling of RBIC or COD's pipe line shall be in manual operation mode only. <br />Transferred Works Inspection 20 Animas -La Plata Project <br />