PUMP STATION ELECTRICAL <br /> The pump station electrical system preliminary design was modified to reflect the <br /> changes described above. One of the 300 horsepower pump starters was eliminated from <br /> the motor control center and the cost of the conduit and wire associated with the third and <br /> fourth pumps was also eliminated. Assuming that a maximum of two 300 horsepower <br /> pumps would be operated at one time, the size of the transformer and main breaker could <br /> be reduced to 1000 KVA capacity. However, there could still be a cost savings by using <br /> the 2000 KVA transformer that is currently owned by Climax if it is available and in good <br /> condition. In addition, it might be advisable to install the larger transformer to provide <br /> potential future flexibility to dredge and return sludge from the seepwater pond. <br /> 4 <br />