Scope of Work <br />18L Air Compressor Building Extension <br />40 Detailed Scope of Work: <br />The scope of work to be completed by the contractor includes: <br />1. Excavate for and Pour Concrete Piers and Slabs: <br />Refer to Figures 1 and Figure 2 — 18L Layout for exact site locations. Refer to Exhibits 1, 3 and 4 for <br />the concrete designs. Concrete work includes an 8" (min.) base slab with outside dimensions of 54'- <br />10" x 24', to be poured around the existing 48' x 8' concrete slab for the air compressors, reinforced <br />with #5 @ 12" each way, centered in the slab thickness, with fourteen 12" diameter bearing piers set a <br />minimum of 6' into bedrock (about 20' total for each pier) reinforced with two #5 verticals. Refer to <br />attached soils report from Northwest Colorado Consultants and the pdf copy of the 18 Left Pad and <br />Pits Cut & Fill drawing for approximate drilling depths. <br />At least 2' of existing soils must be sub - excavated and moisture conditioned to a minimum of 1% over <br />the optimum moisture content, at each pad. These wetted clays are then to be replaced in the over - <br />excavated area in 12" lifts and compacted to 85% of the maximum standard Proctor. These clays must <br />not be over - compacted as it is believed this process should substantially reduce the swelling potential <br />of the clays. <br />• The top of concrete for the pad extension shall match the top of concrete for the existing 48' x 8' air <br />compressor pad and the top of concrete for the existing MCC building. The additional concrete for the <br />fourteen piers approximates 8.1 YD and the additional concrete for the pad extension approximates 23 <br />YD 3 . <br />All concrete is to be poured to a minimum 28 day compressive strength of 3000psi, Type 1. All <br />reinforcing bars will be Grade 60 and shall conform to ASTM Specifications A615 -79. Contractor <br />shall provide for early set concrete and covering of the piers and slab with sufficient heating blankets <br />to keep the concrete warm. <br />After the concrete is completed and the building is erected, the contractor shall return the ground <br />surface to its pre- construction condition with gravels. Final grade shall match current and existing <br />grade around the MCC building. <br />2. Air Compressor BuildinE Extension Construction: <br />Refer to the attached Exhibits 1 through 7. A 54' -10" by 24' steel building extension to enclose the air <br />compressors shall be procured and erected on the poured foundation extension at 18L. The building <br />shall be attached to the existing MCC building (refer to attached CECO building package) and shall <br />have a southern facing sloped roof 12' to 11' with three each, 10' wide by 9' tall, mechanical roll up <br />• doors on the southern side. The building shall also include a 36" man door on the east wall, a 36" man <br />door on the north wall leading from the southwest corner of the existing MCC building, a _ x _ <br />18 left Air Compressor Building Extension Scope of Work 112310.doc Page 3 11/23/10 <br />