Laserfiche WebLink
• <br />Cripple Creek & Victor Gold Mining Company <br />Cresson Project <br />Quality Assurance Monitoring and Test Results <br />Load Out Bin Relocation <br />July 7, 2009 <br />ameO <br />The laboratory test results are summarized in Tables 5, 6 and 7 and presented in Appendix H. <br />4.1.1 Grain Size Distribution <br />AMEC completed the grain size distribution (gradation) of samples of SF, SLF, and DCF. The <br />results of gradation analyses are presented in Appendix H-1 and summarized in Tables 5 <br />through 7. <br />¦ AMEC performed 2 CQA gradations of SF. The testing frequency (approximately one <br />test per 1,000 cubic yards) exceeded the minimum specified testing frequency of one <br />test per 50,000 cubic yards. The CQA gradations performed on SF met project <br />specifications. The SF CQA gradation results are presented in Appendix H-1 and <br />summarized in Table 5. <br />¦ AMEC performed 2 CQA gradations of SLF. The testing frequency (approximately one <br />test per 623 cubic yards) exceeded the minimum specified testing frequency of one test <br />per 5,000 cubic yards. The CQA gradations performed of SLF met project <br />specifications. The SLF CQA gradation results are presented in Appendix H-1 and <br />summarized in Table 6. <br />¦ AMEC performed 3 CQA gradations of DCF. The testing frequency (approximately one <br />test per 1,075 cubic yards) exceeded the minimum specified testing frequency of one <br />test per 20,000 cubic yards. The DCF CQA gradations met project specifications, and <br />the results are presented in Appendix H-1 and summarized in Table 7. <br />4.1.2 Moisture Content <br />9 <br />AMEC measured oven moisture contents of SF, SLF, and DCF as part of the CQA program. <br />Moisture content data are presented in Appendix H-1. <br />4.1.3 Atterberg Limits <br />AMEC performed Atterberg limit testing of all fill materials. All fill materials, with the exception of <br />SF and SLF were non-plastic. The SLF, SF, and DCF samples tested met project specifications <br />for Atterberg Limits. <br />The SLF Atterberg limits testing frequency (approximately one test per 623 cubic yards) <br />exceeded the minimum specified testing frequency of one test per 5,000 cubic yards. The <br />plasticity index of the CQA SLF samples were both 29, meeting the project specification of <br />plasticity index greater than or equal to 10. Atterberg limit test results for SLF are presented in <br />Appendix H-1 and summarized in Table 6. <br />S:\PROJECTS\1125E CCV CQA\H3 - CONSTRUCTION\LOB CERT REPORT\REPORT BODY\LOB CERT REPORT 2009.07.07.DOC <br />11