Laserfiche WebLink
PART I <br />Page lki of 14 <br />Permit No. CO-0027154 <br />B. MONITORING REQUIREMENTS <br />2. Frequency and Sample Type For Outfalls 002, 003 004 006, 008, 009 010 016 017 and <br />020 <br />c) Outf all 020 <br />Parameter Monitoring Frequency Sample Type <br />Flow, MGD Weekly Instantaneous <br /> or Continuous <br />TSS, mg/P Three/Month Grab <br />TR Iron, mg/P Three/Month Grab <br />TR Manganese, mgP Three/Month Grab <br />PD Copper, mg/P Three/Month Grab <br />PD Silver, mg/P Three/Month Grab <br />Oil and Grease, mg/P Weekly Visual <br />pH, s.u. (Minimum-Maximuml Weekly Grab <br />Total Dissolved Solids, mg/P Three/Month Grab <br />WET, Chronic Lethality Quarterly 3 Grabs/Test <br />Sampling for compliance with the monitoring requirements specified above shall be <br />performed at the following location: the outfall from the final pond, prior to <br />entering Foidel Creek. <br />See Part I.D. for Footnotes <br />Amendment No. 4 Issued Effective <br />