Laserfiche WebLink
.~ <br />SPCC Pi.=1V REVISION <br />FE3R!I.R'i , 1995 <br />1. There has rot been a repo-table oil or ch_mical swill event at <br />this facility during the pre-:ious twelve month period. A 350 <br />gallon hydrochloric acid spill which occurr=_d in November, 1954, <br />did got meet .he minimum cuantity for a reportable event. The <br />spill was quickly contained and cleaned up. There was no release <br />of the chemical into the river or other waters of the State. <br />2. Material storage tanks are located in the following above <br />ground locations; <br />A. 1 10,000 <br />B. 1 '0,000 <br />• C. 2 1,000 <br />D. 1 5,000 <br />E. 1 x,000 <br />F. 1 1, X00 <br />G. 1 5,000 <br />H. 1 3, 100 <br />I. 1 5,000 <br />~. 1 3,000 <br />K. 1 5,000 <br />Gallon <br />Gallon <br />Gallon <br />Gallon <br />Gallon <br />Gallon <br />Gallon <br />Gallon <br />Gallon <br />Gallon <br />Gallon <br />Diesel Fuel @ East Yard <br />Gasoli;.e Tank @ East Yard <br />Diese~ Fuel @ Prep Plant <br />Acid Tank @ Plant Thickener <br />Waste Oil @ Oil House <br />Waste Oil @ Oil House <br />Deicer @ Breaker Building <br />Deicer @ Silo <br />Cation @ Prep Plant <br />Floc @ Prep Plant <br />Macjnesium Chloride @ East Yard <br />3. Tanks are constructed of welded steel or.polyethylene and in <br />good condition. In the event of an uncontrolled release from one <br />of these tanks, the material would not spill into the Purgatoire <br />River. A11 locations are such that drainage would report to a <br />sedimentation pond with a gated valve discharge. The valve-would <br />not_be opened:in the case of a spill_ _ __ _--- <br />4. Oil storage tanks at the indicated facilities are located~in <br />such a manner that any potential discharge will be contained in an <br />impoundment or enclosure with a capacity at least 10 percent <br />greater than the capacity of the largest tank in a group of tanks. <br />5. A gate valve is provided at the bottom of the concrete or <br />steel secondary containment facilities to periodically drain <br />rainwater. Impoundments used as containment facilities will be <br />. equipped with adequate baffles, oil containment booms or an <br />adequate oil skimmer on the dewatering device to ensure retention <br />of the oil from the largest tank. <br />Y <br /> <br />