ACUREN <br /> Item Status comments <br /> 0.0 Venting <br /> 8.1 Vents free of obstructions? ❑ X Yes ❑ No* PRODUCT RESIDUE EXISTS AROUND VENT BUT IS NOT CLOGGED. <br /> 8.2 Emergency vent operable? <br /> Lift as required? u Yes a No* u X NIA <br /> 9.0 Insulated Tanks <br /> 9.1 Insulation missing? ❑Yes* ❑ No X NIA <br /> 9.2 Are there noticeable areas of <br /> moisture on the Insulation? ❑Yes* ❑ No X NIA <br /> 9.3 Mold on insulation? uYes* ❑ No X WA <br /> 9.4 Insulation exhibiting dam ? ❑Yes* ❑ No X NIA <br /> 9.5 Is the insulation sufficiently <br /> protected from water intrusion? ❑Yes ❑ No*X NIA <br /> 10.0 Level and Overfill Prevention Instrumentation of Sha -Fabricated Tanks <br /> 10.1 Has the tank liquid level <br /> sensing device been tested to <br /> ensure proper operation? ❑ Yes ❑X No* WA ELECTRONIC LEVEL APPEARS TO BE IN GOOD CONDITION VERIFY ACCURACY. <br /> 10.2 Does the tank liquid level <br /> sensing device operate as <br /> req ui red? ❑Yes ❑ No* X WI <br /> 10.3 Are overfill prevention <br /> devices in proper working <br /> condition? ❑Yes ❑ No* ❑ X NIA <br /> 11.0 Electrical Equipment <br /> 11.0 Are tank grounding lines in <br /> good condition? ❑X Yes ❑No* ❑ NIA <br /> 11.2 Is electrical wiring for control <br /> boxesAi hts in good condition? ❑ X Yes ❑ No* ❑ WA <br /> RECOMMENDATIONS <br /> 1. REPAIR OR REPLACE FITTING THAT IS LEAKING. <br /> 2. COATIREPAIR CRACKS IN CONCRETE CONTAINMENT AND FOUNDATION. <br /> 3. PERFORM PERIODIC INSPECTIONS AS OUTLINED IN STI-SPOOL. <br />