Laserfiche WebLink
2.0 POTENTIAL SPILL SOURCES <br /> 2.1 Facility Storage <br /> Note: In this section describe all types of oil product storage at your facility including oil products <br /> stored in aboveground storage tanks (ASTs), underground storage tanks (USTs), oil-filled electrical <br /> equipment (e.g., circuit breakers, transformers), spill tanks, oil/water separators, vapor recovery units <br /> portable tanks, drum storage, and trucks which hold oil product and are parked on site. <br /> Typical locations of each tank/container listed below can be found in Appendix 1 (Site <br /> Layout). There are no buried or bunkered tanks associated with this portable plant. <br /> Above Ground Storage Tanks <br /> Tank Max. Method of <br /> ID Location Capacity Contents Secondary <br /> (gallons) Containment <br /> 1 AC Trailer 30,000 Asphalt Cement Inside berm <br /> 2 AC Trailer 30,000 Asphalt Cement Inside berm <br /> 3 Diesel Trailer 10,000 Diesel Fuel Inside berm <br /> 4 Diesel Trailer 10,000 Burner Fuel Inside berm <br /> 5 Generator Truck Diesel Tank 750 Diesel Inside berm <br /> Motor and <br /> 6 Sides of Diesel Trailers 250 x 5 Hydraulic Oils Inside berm <br /> (15W40, THF 1000, <br /> 30 Wt.) <br /> 55 GALLON DRUMS <br /> LOCATION I #_OF I PRODUCT CONTAINMENT &SPILL CONTROL <br /> DRUMSI FEATURES <br /> Generator 8 Misc. oils, Antifreeze Located in generator trailer within berm <br /> Trailer ,(varies) <br /> Portable Gencor Asphalt Plant Page 3 <br /> SPCC Plan August 31, 2005 <br />