Mr. Jack Henris <br />July 28, 2016 <br />Page 2 <br />m:\min\tc1\_teller\m-1980-244 cc-v\tr-80 tempwtrline\m-80-244-tr80par2016-07-28.docx <br /> Lines to be identified in Comment No. 2 (shown by arrows) <br />3) Pipe Specifications. The pipe specifications indicate the discharge pressure at the pump <br />is expected to be 275 psig. Two specifications are given for 8-inch diameter HDPPE <br />pipe: DR 11 and DR 07. A quick reference to HDPE pipe standard specifications <br />indicate DR 07 is rated for 333 psi. However DR 11 is rated for 200 psi. Please explain <br />why how the two different pipes will be installed to ensure adequate pressure ratings <br />for the system. <br />4) Schedule. The schedule indicates “replacement fresh water line from Grassy Valley is <br />expected to be in place by the middle of November 2016, minimizing freezing <br />concerns.” The Division is concerned about potential delays in construction for the <br />permanent replacement line. How does CC&V intend to mitigate potential problems <br />due to freezing if there is a significant delay in the construction of the permanent water <br />line? <br />5) Reclamation cost estimate. The TR-80 submittal did not include a demolition cost for <br />the temporary water line. Please provide a demolition cost estimate. <br />