<br />year 1991. Fire flow or water storage for fire protection is computed <br /> <br />using the following equation: <br /> <br />Flow in Gallons = 1020/1' (1 - 0.01 vI' ) <br /> <br />(where P is equal to population in thousands). The total recommended <br /> <br />storage requirements are for the years 1976 through 1991 and are tabulated <br /> <br />in Table VII-A. <br /> <br />TABLE VII-A <br /> <br />. <br /> <br />Storage Requirements <br /> <br /> Projected 120% Maximum Fire Flow Emergency Total Required <br />Year Population Day Demand Storage Storage Storage <br />1976 1,080 505,200 629,400 283,700 1,418,300 <br />1977 1,120 519,600 640,800 290,100 1,450,500 <br />1978 1,180 559,200 657,600 304,200 1,521,000 <br />1979 1,240 589,200 673,900 315,800 1,578,900 <br />1980 1,280 620,400 684,600 326,250 1,631,300 <br />1981 1,360 652,800 705,400 339,600 1,697,800 <br />1982 1,400 687,600 715,600 350,800 1,754,000 <br />1983 1,490 723,600 738,000 365,400 1,827,000 <br />1984 1,550 762,000 752,500 378,600 1,893,100 <br />1985 1,665 801,600 779,500 395,300 1,976,400 <br />1986 1,750 843,600 799,000 410,600 2,053,200 <br />1987 1,845 888,000 820,000 427,000 2,135,000 <br />1988 1,940 934,800 840,500 443,800 2,219,100 <br />1989 2,045 984,000 862,700 461,700 2,308,400 <br />1990 2,150 1,035,600 884,200 480,000 2,399,800 <br />1991 2,260 1,087,200 906,200 498,400 2,491,800 <br /> <br />It .is shown by Table V1I-A that a storage facility of approximately <br /> <br />. <br /> <br />2,000,000 gallons will be required by the year 1991. A storage facility <br /> <br />of this capacity should be constructed at the location as shown on Exhib- <br /> <br />it C. This storage would not only se~ve the development North of the Eagle <br /> <br />River, but would be connected with the town's present system to furnish <br /> <br />water for the whole system. This again would provide water storage at the <br /> <br />opposite end of the system from the primary supply. <br /> <br />There are two ways in order for the town to get the full storage capac- <br /> <br />ity of the new 200,000 gallon tank constructed just East of the cemetery: <br /> <br />(1) with the installation of valves and a telemetering system (2) or the <br /> <br />- 44- <br />