Laserfiche WebLink
<br /><;i '! <br /> <br />1994 Master Plan Update <br />Town of Elizabeth <br /> <br />TABLE 2 <br />UNIT WATER DEMANDS <br /> <br />Demand gpcd gpd/SFE ac-ft/yrlSFE PF <br />Recommended <br />AD 95 295 0.33 <br />MD 258 800 2.7 x AD <br />PH 570 1.770 6.0 x AD <br />1988 Master Plan <br />AD 85 264 0.30 <br />MD 255 792 3.0 x AD <br />PH 510 6.0 x AD <br /> <br />AD :::: Average Day <br />MD:::: Max Day <br />PH :::: Peak Hour <br />PF :::: Peak FactoT <br />gpcd :::: gallons per person per day <br />gpd/SFE :::: gallons per day per single-family equivalent <br />ac-ft/yr/SFE :::: aCTe-feet per year per single-family equivalent <br /> <br />Water System Criteria <br /> <br />The design criteria recommended for the water system supply and stoTage <br />facilities is outlined below. <br /> <br />SUPPLY CRITERIA: <br />Supply Flow :::: Max Day Demand (gpm) + Safety Factor <br /> <br />STORAGE CRITERIA: <br />Storage Volume :::: [Peak Hour Demand x 8 hOUTS] + Fire Flow <br />+ Safety Factor <br /> <br />Meurer & Associates <br />October 5. 1994 <br />Page 4 <br />