tCA l E <br />Figure 4.18 -5 Typical Distribution Three -Phase Pole Configuration. <br />Location of implementation for: <br />POLE -TOP GROUND MOLDING <br />EAGLE <br />MEASUREMENTS <br />r <br />CONDUCTOR -�` INSUFFICIENT EAGLE <br />CLEARANCE <br />V- i <br />p O <br />8' 40' <br />8' WOOD <br />CROSSARM <br />NEUTRAL Location of implementation for: <br />PERCH GUARDS AND BIRD <br />SPIKES <br />Typical distribution three -phase pole configuration. <br />Three -phase power lines are usually constructed with an 8 -foot crossarm supporting two <br />conductors. A single energized phase conductor typically sits on a pole -top insulator. <br />Distribution three -phase tangent structures, without pole -top grounds or pole -top mounted <br />equipment, generally provide adequate separation for all but the largest raptors since 44 inches of <br />phase separation is provided. There is also a 20- degree angle between the outer and center phase <br />wires. This separation is appropriate in areas where large raptors are less likely to occur. In areas <br />where eagles use these poles as preferred perches, additional protection to minimize the <br />electrocution risk would be required. A couple of different raptor protection device alternatives <br />and their locations are shown above in Figure 4. <br />Figures 37 Revision Date: 6/12/12 <br />Revision No.: RN -06 <br />