Laserfiche WebLink
Test and <br />ASTM <br />Designation <br />Low Volume Solution Collection Fill, Bedding <br />Fill, Leak Detection FM, <br />and Pipe Bedding Fill <br />(cy) <br />Soil Liner <br />Fill <br />(cy) <br />Drain Cover <br />Fill <br />(cy) <br />Compaction <br />(ASTM D698) <br />-- <br />5,000 <br />-- <br />Particle Size2 <br />(ASTM C117, C136, <br />D1140) <br />10,000 <br />5,000 <br />20,000 <br />Atterberg Limit <br />(ASTM D4318) <br />10,000 <br />5,000 <br />20,000 <br />Moisture Content3 <br />(ASTM D2216) <br />10,000 <br />500 <br />20,000 <br />Permeability4 <br />(ASTM D5084/2434) <br />-- <br />5,000 <br />-- <br />Nuclear Density <br />-- <br />500 <br />-- <br />• <br />• <br />S: \Projects \1125E CCV CQA \I - Tech Specs \01400.1.r1.doc <br />* ** END OF SECTION * ** <br />ame <br />1. Tests shall be performed at the specified frequency or one per material type, whichever is greater. <br />2. Use the USCS for description and identification (ASTM D2488). <br />3. In -place Moisture Content. <br />4. If the permeability of Soil Liner Fill is higher than 9.0x10 -7 cm/sec, an additional permeability test will be <br />performed on a sample located within a 10 foot radius of the sample in question. If the permeability of the <br />Soil Liner Fill is higher than 1.0x10 -6 cm/sec, 4 additional samples will be obtained from with 135,000 <br />square foot area centered about the failing test. This testing sequence will be repeated if additional failing <br />permeability tests are measured. <br />Section 01400.1 Page 9 of 9 September 3, 2008 <br />Earthworks CQA Plan Revision 1 <br />