....... <br />_... _..... ......... <br />• ? www.energylab.com -Helena, IVIT 877-472-0711 • Billings, W 800-735-4489 • Casper, WY 888-235-0515 <br />AwtytivlErcebmSir" IOU ! Gillette, WY 866-686-7175 • Rapid City, SO 888-672-1225 • College Station, TX 888-690-2218 <br />QA/QC Summary Report <br />Client: Cotter Corporation Report Date: 09/16/10 <br />Project: Schwartzwalder Water Monitoring Program Work Order: C10080658 <br />Analyte Count Result Units RL %REC Low Limit High Limit RPD RPDLimit Cual <br />Method: A4500-F C Batch: R136361 <br />Sample ID: MBLK Method Blank Run: MANTECH_100823A 08/23/10 08:56 <br />Fluoride ND mg/L 0.05 <br />Sample ID: LCS Laboratory Control Sample Run: MANTECH_100823A 08/23/10 08:59 <br />Fluoride 1.02 mg/L 0.10 102 90 110 <br />Sample ID: C10080223-005AMS Sample Matrix Spike Run: MANTECH_100823A 08/23/10 09:12 <br />Fluoride 1.31 mg/L 0.10 103 80 120 <br />Sample ID: C10080223-005AMSD Sample Matrix Spike Duplicate Run: MANTECH_100823A 08/23/10 09:15 <br />Fluoride 1.34 mg/L 0.10 106 80 120 2.3 10 <br />Qualifiers: <br />RL - Analyte reporting limit. <br />MDC - Minimum detectable concentration <br />ND - Not detected at the reporting limit. <br />Page 8 of 25