Laserfiche WebLink
Case Narrative <br />Analytica Environmental Laboratories, Inc. <br />Work Order: B1009086 <br />(continued) <br />This analysis was performed as soon as possible upon laboratory receipt. <br />HOLD TIMES MISSED: <br />Sample LSSW010,A1009046-01B <br />Sampled: 9/2/2010 10:25:00 AM, Prepped: 9/15/2010 10:00:00 AM <br />Sampled: 9/2/2010 10:25:00 AM, Analyzed: 9/15/2010 1:22:43 PM <br />Regulatory hold time: 48 Hrs <br />Sample CDP-DIS,B1009086-01C <br />Sampled: 9/9/2010 12:00:00 PM, Prepped: 9/15/2010 10:00:00 AM <br />Sampled: 9/9/2010 12:00:00 PM, Analyzed: 9/15/2010 8:59:14 PM <br />Regulatory hold time: 48 Hrs <br />Sample CDP-DIS,B1009086-01C <br />Sampled: 9/9/2010 12:00:00 PM, Prepped: 9/15/2010 10:00:00 AM <br />Sampled: 9/9/2010 12:00:00 PM, Analyzed: 9/16/2010 6:03:08 PM <br />Regulatory hold time: 48 Hrs <br />SAMPLE PREPARATION ISSUES AND OBSERVATIONS: <br />There were no unusual observations. <br />METHOD BLANK OUTLIERS: <br />There are no method blank outliers. <br />LCS OUTLIERS: <br />There are no LCS outliers. <br />MS/MSD and DUP OUTLIERS: <br />There are no MS/MSD or DUP outliers. <br />Test Method: SM4500-CNE - Cyanide, Colorimetric Method - Total CN - Drinking Water <br />HOLDING TIMES: <br />Holding times were met for this test. <br />SAMPLE PREPARATION ISSUES AND OBSERVATIONS: <br />There were no unusual observations. <br />METHOD BLANK OUTLIERS: <br />There are no method blank outliers. <br />LCS OUTLIERS: <br />There are no LCS outliers. <br />MS/MSD and DUP OUTLIERS: <br />There are no MS/MSD or DUP outliers.