Laserfiche WebLink
PART 2 — PRODUCTS <br />2.1 MATERIALS <br />A. POLYVINYL CHLORIDE (PVC) PIPE <br />1. Pressure Pipe (Underground Piping) <br />2. ASTM D2241, SDR 26 Class 160 PVC <br />3. Joint Type: Gasket bell end <br />4. Pipe size indicated on Drawings <br />B. STEEL PIPE <br />1. Standard: AWWA C200 -05 <br />2. Pipe size indicated on Drawings <br />3. Flanged pipe (above ground only, not for direct bury); AWWA C207 -07 <br />a. Pipe below ground shall be have a protective coating per <br />AWWA C203 -02 or C209 -06 <br />C. Fittings <br />1. Material: Ductile (Underground), AWWA C110; Steel (Above Ground Only) AWWA <br />C207 -07 <br />2. Type: Tyler Union <br />a. As shown on Drawings or otherwise required by Specifications <br />3. Pressure rating <br />a. 12" and under: 350 psi <br />D. Joints <br />1. Mechanical and Push -on (Underground) <br />a. Standard: AWWA C111 <br />b. Gaskets: Synthetic Rubber <br />1) Lubricant as required and recommended per manufacture <br />2. Flanged (Above Ground Only) <br />a. Standard: AWWA C207 -07 <br />b. Gaskets: Synthetic Rubber <br />E. Protective Coatings and Linings <br />1. Underground Service <br />a. Shop coatings and linings <br />1) Tape: AWWA C209 -06, C214 -07 <br />2) Bituminous coating: Manufacturer's recommendations; AWWA C218 -08 <br />F. Restrained Joints <br />1. Material: ASTM A -36 steel all- thread, cadmium plated <br />2. Bolts: Tyler Union or equal <br />09211111111W <br />