Laserfiche WebLink
r"erg-e I <br />, 11 - Ni <br />F. Where pipe sleeves, inserts, and anchors prevent placement of reinforcing bars in the locations shown, <br />additional reinforcing shall be required, in locations as approved by CERTIFYING ENGINEER. <br />G. Reinforcing bar splices shall be used only in the locations shown on the DRAWINGS. <br />H. Welded splices shall not be permitted. <br />I. The length of lap for reinforcing bars shall be in accordance with ACI 318, unless otherwise shown. <br />* ** END OF SECTION * ** <br />• <br />0 <br />Section 03220 Page 2 of 2 September 3, 2008 <br />Reinforcing Steel Revision 0 <br />S: \Projects \7125E CCV CQAU - Tech Specs \03220.r0.doc <br />