Laserfiche WebLink
El <br />9AC <br />SMITH WILLIAMS CONSULTANTS, INC. <br />SOIL CONSTRUCTION TESTING FREQUENCY <br />VOLUME PER TEST' <br />• <br /> Low Volume Solution Collection Fill, Bedding <br />Test and Fill, Leak Detection Fill, Soil Liner Drain Cover <br />. ASTM and Pipe Bedding Fill Fill Fill <br />Designation c c c <br />Compaction -- 5,000 -- <br />ASTM D698 <br />Particle Size2 <br /> 10,000 5,000 20,000 <br />(ASTM C117, C136, <br />D1140 <br />Atterberg Limit 10,000 5,000 20,000 <br />(ASTM D4318) <br />Moisture Contene <br /> <br />(ASTM D2216) 10,000 500 20,000 <br />Permeability4 <br /> 5,000 -- <br />ASTM D5084/2434 <br />Nuclear Densi -- 500 -- <br />1. Tests shall be performed at the specified frequency or one per material type, whichever is greater. <br />2. Use the USCS for description and identification (ASTM D2488). <br />3. In-place Moisture Content. <br />4. If the permeability of Soil Liner Fill is higher than 9.0x10-7 cm/sec, an additional permeability test will be <br />performed on a sample located within a 10 foot radius of the sample in question. If the permeability of the <br />Soil Liner Fill is higher than 1.0x10-6 cm/sec, 4 additional samples will be obtained from with 135,000 <br />square foot area centered about the failing test. This testing sequence will be repeated if additional failing <br />permeability tests are measured. <br />*** END OF SECTION *** <br />Ell <br />Section 01400.1 <br />Earthworks CQA Plan <br />Page 9 of 9 <br />March 14, 2008 <br />Revision 0 <br />SAProjecfs\1125 CCBV Phase 5 VLFU - Tech SpecsV\requa\01400.1.r0.doc