NOR't.,~11EST COLORADO CONSULTAN i.i, INC. <br />FIELD REPORT <br />Project: Sectlon 28 Pond Project No.: 07-7fi49 <br />Location: Colowyo Mine Report No.: 6 <br />Client: Anson Excavating & Pipe <br />Date: 9/12(07 <br />Time: 5.0 <br />Mileage: 109 <br />Engr.ITech: RE <br />Work Performed: <br />As requested, we visited the project site on this date and conducted compaction test No.'s 26 through 28, as well <br />as re-test No.'s 26A, 27A and 28A on the material being placed for the Section 28 Pond keyway trench backfill. <br />Ttre excavation contractor, Anson Excavation and Pipe, placed, moistened and compacted on-site materials along <br />the keyway trench. <br />We obtained two samples of the materials located at the possible borrow area to the west of the pond site and <br />returned them to our laboratory for standard Proctor and classification testing. The upper sample will be referred to <br />as Proctor Sample Number 9P for this project and the lower sample will be referred to as Proctor Sample Number <br />10P. <br />Remarks: <br />The material tested appeared to not be adequately mixed at the time of initial testing, which led to low compaction <br />results. The contractor then excavated and re-mixed the lift before recompacting. Upon re-tes#ing the materials <br />appeared to be properly compacted and uniformly moistened. <br />The material tested generally met the project specifications for compaction and moisture content. <br />Please refer to the attached sheet for results of todays testing. <br />Verbal Discussions: <br />Dusty Wiseman of Anson Excavating was notified of today's test results. <br />Att. A3-3 <br />