Laserfiche WebLink
<br />7. The operators of the facility need to be made aware of <br />the hazards of work activities in proximity (within the <br />easement) of the high voltage transmission line, particularly <br />when using boom equipment, and should do so at their own <br />risk. The line design has been based on a maximum vehicle <br />height of 14 feet. <br />8. In the interests of Safety, I am averse to use of the <br />easement for the asphalt haul road. If this asphalt <br />road is a must along the easement, then (a) the road <br />should be built such that the transmission line does <br />not overhang any part of the road and (b) the nearest <br />edge of the road is at least 20 feet from the nearest <br />line support pole; if the road is built closer than <br />20 feet to the pole, then appropriate traffic safety <br />barriers would be needed at the poles. <br />SP:lm <br />cc: Bob Baldridge Suresh Patel <br />John Barber Jim Phillips <br />Ron Ostop Chuck Weir <br />Larry Patterson <br />