Laserfiche WebLink
r- <br /> <br />APT Project CMX2453 <br />Test Report, Kiln Stack Emissions (March 24, 2003) <br />~CEMEX :Lyons, Colorado -Kiln Stack (Coal Fired Only) <br />Aldehydes and Trace VOCs Emissions Testing Results, 11/15/2002 and 11/22/2002 <br /> Run #1 Run #2 Run 1k? gverage <br />Date 11 /15/02 11 /15/02 11 /22/02 <br />Start Time I'I 10:36 13:14 11:52 <br />Stop Time ~'~ 12:01 14:39 13:06 <br />Production Data <br />Kiln Raw Feed Rate (tons per hour) 100.0 100.1 107.0 102.4 <br />Stack Gas Parameters <br />Stack Temp. (°F) 400 401 410 404 <br />Stack Flow (kdscfm) 135.4 152.6 148.1 145.3 <br />OZ (%vd) 12.0 12.0 11.0 11.7 <br />COZ (%vd) 13.6 13.8 15.4 14.3 <br />H2O (%vw) 18.1 17.8 18.1 18.0 <br />Isokinetic 103.4 102.1 104.1 103.2 <br />Emissions Data <br />formaldehyde (Ib/hr) 4.03E-02 5.88E-02 5.53E-02 5.15E-02 <br />acetaldehyde (Ib/hr) 3.94E-03 4.29E-03 2.00E-01 6.94E-02 <br />carbon disulfide (Iblhr) f21 N/A N/A 3.13E-02 3.13E-02 <br />methylene chloride(Ib/hr)~2~ N/A N/A 3.91E-03 3.91E-03 <br />benzene(Ib/hr)t2t N/A N/A 3.21E-03 3.21E-03 <br />bromomethane (Ib/hr)121 N/A N/A 4.60E-03 4.60E-03 <br />1,4-dioxane (Ib/hr)121 N/A N/A 2.56E-02 2.56E-02 <br />ethanol (Iblhr)121 N/A N/A 5.35E-03 5.35E-03 <br />These are the start/stop times for aldehydes sampling. See Appendix 1 for trace VOCs <br />sampling. <br />I21 The results from the first two TO-14 runs indicate improper sampling, resulting in u nreasonable <br />levels of acetone. Therefore, these run s have been voided. The averages for the detected trace <br />VOCs are the Run #3 results. <br />Table 2.5: Test Results Summary -Aldehydes and Trace VOCs (Coal Fired Only) <br />page 7 <br />