Laserfiche WebLink
' Table 1 <br /> Summary of Parameters, Sample Containers, <br /> ' Holding Times, and Analytical Methods <br /> Parameter Matrix No.and Type of Holding Time(1) Analytical <br /> ' Containers Method(2) <br /> Alkalinity <br /> Water 1-100 ml P,G <br /> 14 days cool to 4C SM 2320H <br /> Chloride <br /> Water 1-200 ml,P,G <br /> ' 28 days no preservative required EPA 300.0 <br /> Fluoride <br /> Water 1-500 and, P <br /> ' 28 days no preservative required EPA 300.0 <br /> Sulfate <br /> ' Water I -200 ml,P <br /> 28 days cool to 4C EPA 300.0 <br /> NitraleMilrite <br /> ' Water I - 100 ml,P,G <br /> 48 hours cool to 4C EPA 300.0 <br /> 1-500 ml KG <br /> ' Mercury Water 28 days,HNO3 to pH<2 245.1/7170 <br /> ' Total Metals(RCRA) <br /> Water 125-500 ml nalgene(Red 6 months except Mercury at 28 days. For <br /> dot) water,preserved with HNO3,not filtered. 601017000 <br /> Dissolved Metals(RCRA) <br /> Water 125-500 ml nalgene 6 months except Mercury at 28 days. Filtered 6010/7000 <br /> and preserved in Lab. <br /> ' Anions/General Chemistry <br /> Water 250 ml nelgene 28 days 200 Series <br /> ' Notes: (1)All collected samples to be kept cool(4 degrees C) (2)USEPA Method,S W-846(Revised). 1986 <br /> 1 <br />