Laserfiche WebLink
~. - <br />'~ ~~~ COMMERCIAL TESTING L~ ENGINEE RING CO. <br />a COLORADO - CDPS WET TEST REPORT FORM -CHRONIC <br />1 PERMITTEE Rae America Empire CDPS NO. CO-0034142 OUTFACE: SD <br /> <br />J <br /> <br />7 <br /> <br />7 <br />J <br /> <br />,1 <br />TYPE TEST: ROUTINE: XX ACCELERATED: TEST SPECIES: C. dubia <br />TEST RESULTS LETHALITY REPRODUCTION STATLSTICAL METHOD <br />Concentration with Statistical Difference >100% >100% Fisher'slDunnett's <br />Pass/Fail Pass N/A <br />ICZS >]00% >100% Bootstra <br />Pass/Fail Pass N/A <br />TEST TIME & DATE START 1050 AM 09/17/02 END 1140 AM 09/25/02 <br />DILUTION (% EFFLUENT) <br />MEASUREMENTS CONTROL 11.5% 25% 50% 75% 100% <br />Day 1 % Survival 100 100 100 100 100 100 <br />Da 2 100 100 100 100 100 100 <br />Da 3 100 100 100 100 100 100 <br />Da 4 100 100 100 100 100 100 <br />Da 5 100 100 100 90 100 100 <br />Da 6 80 100 100 90 100 90 <br />Da 7 80 100 100 90 100 90 <br /> <br />Mean 3 Brood Total 18.1 16.3 17.0 15.3 15.8 16.9 <br /> <br />pH (Maximum/Minimum) 8.8/8. ] 9.0/8. l 9.1/8.0 9.2/7.8 9.2/7.7 9.2/7.7 <br />RECEIVING WATER USED FOR DILUTION? NO TOTAL RESIDUAL CI" (mg/I): <O.l <br />HARDNESS (mg/11: REC'V WATER: EFFLUENT: 72 RECON WATER: 112 <br />ALKALINITY (mil: REC'V WATER: EFFLUENT: 753 RECON WATER 82 <br />TOT. AMMONIA (mpJl): INITIAL 100%: <1.0 FINAL 100%: <1.0 <br />WERE ALL TEST CONDITIONS IN CONFORMANCE WITH DIVISION GUIDELINES? NO <br />IF NO, LIST DEVIATIONS FROM TEST SPECIFICATIONS: Kit #3 was not delivered within the orooer <br />holdinp_ time due to a shipping error on the Hart of UPS. A portion of kit #2 sample was used for day-5 <br />renewal. /+ ~ <br />LABORATORY: COMMERCIAL TESTING & ENGINEERING ANALYST: CiyC.~.~`_-i~~`~ ~--~ <br />:52f <br />