Laserfiche WebLink
PART I <br />Page lj of 19 <br />Permit No. CO-0000132 <br />B. MONITORING REQUIREMENTS <br />11. Special Monitoring - One Time Analysis <br />In order to determine the general quality of water discharged at this <br />facility, the permittee is required to perform a one time analysis for <br />the following parameters at the specified discharge point. The <br />monitoring and analysis shall be performed at the first instance of <br />discharge after this permit becomes effective. Following analysis, <br />the data shall be submitted to the Permits and Enforcement Section, <br />within forty-five (45) days of the sampling date. <br />Parameter <br />Disch. Sample Maximum Acceptable <br />Point Type e/ Detection Limit <br />Oil and Grease, mg/1 011 Grab 5 <br />Alkalinity, mg/1 011 Grab 10 <br />Total Arsenic, mg/1 011 Grab 0.05 <br />Total Recoverable Cadmium, mg/1 011 Grab 0.0604 <br />Total Recoverable Chromium, mg/1 011 Grab 0.005 <br />Total Recoverable Copper, mg/1 011 Grab 0.005 <br />Total Recoverable Iron, mg/1 011 Grab 0.3 <br />Total Recoverable Lead, mg/1 011 Grab 0.005 <br />Total Recoverable Manganese, mg/I 011 Grab 0.05 <br />Total Mercury, mg/1 011 Grab 0.00025 <br />Total Recoverable Nickel, mg/1 011 Grab 0.05 <br />Total Selenium, mg/1 011 Grab 0.0002 <br />Total Recoverable Silver, mg/1 011 Grab 0.0002 <br />Total Recoverable Zinc, mg/1 011 Grab 0.05 <br />Dissolved Manganese, mg/1 011 Grab 0.05 <br />Dissolved Iron, mg/1 011 Grab 0.3 <br />Total Residual Chlorine, mg/1 011 Grab 0.05 <br />Nitrate as N, mg/1 011 Grab 0.1 <br />Nitrite as N, mg/1 011 Grab 0.002 <br />Boron, mg/1 011 Grab 0.05 <br />Chloride, mg/1 011 Grab 5 <br />Sulfate, mg/1 011 Grab 5 <br />Sulfur as H2S 011 Grab 0.1 <br />If evaluation of the data demonstrates a definite or probable <br />violation of water quality standards, the permit may be amended to <br />incorporate additional monitoring and limitations, as allowed under <br />Part II.B.S of this permit. Additional monitoring may also be <br />required where the detection limit fora parameter is above the <br />appropriate water quality standards. <br />See Part I.C. for Footnotes. <br />