Laserfiche WebLink
PART I <br />Page 11 <br />Permit No. COG~i00000 <br />B. TERMS AND CONDITIONS <br />2. Efflurnt Limitations (coat.) <br />f. Facilities discharging non-contact cooling or heating wazer shall comply with the following <br />limitations unless additional monitoring is imposed by the Division. See the facility <br />certification for a complete list of parameters and limitations. <br />Effluent Parameter Discharee Limitations <br /> 30_Dav Ave 7-Dav Ave Daily Max <br />Flow, gpm RepotUSee I.B.2.k. NA Report <br />Total Suspended Solids, mg/P 30 45 NA <br />Temperature, °C NA NA See Table I.B.-1 <br /> below <br />Total Residual Chlorine, mg/f See V.B.1. of the NA Sce V.B.1. of the <br /> rationale and the razionale and the <br /> equation in equation in <br /> I.B.2.c.(1) of the I.B.2.c.(1) of the <br /> permit permit <br />Total Phosphorus as P, mg/P See I.C.2. NA NA Report <br />1Lis diseharge ntegory allows for the exemprion of monitoring for facilities drat consistendv discharge 5 gpm or less for a maximum of one <br />hoof or 300 gallotu mml. See Part I.C3. of the permit for rem~..m...t~, <br />pH - standazd units shall remain between 6.5 and 9.0. <br />Oil and Grease sball no[ excced 10 mg/f. <br />Sce Best Management Practices, I.F.S. <br />This parameter is based on the Aquatic Life Classification of the receiving water. The following limits will apply: <br />Table I.B: I <br />'.: Cla.~l:.Cold:: ':'::::'::. Class T.Watm:":• :..: ::::: ::::..:Class2:Cold:and:Warm`::;::-:; <br />Maximum 20°C Maximum 30°C Monitor <br />See Part V.B.3. o[ the cermit rationale <br />