Laserfiche WebLink
PART I <br />Page 4 of 19 <br />C. FOOTNOTES <br />1/ - When the moat sensitive analytical method which complies xith Part <br />I.P.2. of the permit bas a detection limit great es than or equal to <br />the permit limit, the parmittea shall report 'less than the <br />detectable limit', as appropriate. Such reports shall not be <br />_ considered as violations of the permit limit. <br />The present lowest method detection limit for specific parameters <br />(rhich have limitatiooa which era, in some cases, less than or equal, <br />to the detection limiC) are as folloxs: <br />Total Residual Chlorine 0.05 mg/1. <br />Total Recoverable Cadmium 0.0003 mg/1 <br />Total Recoverable Coppai 0.005 m8/1 <br />Total Recoverable Lead 0.005 mg/1 <br />Total Mercury 0.00625 mg/1 <br />Total Recoverable Nickel 0.05 mg/1 <br />Total Recoverable Silver 0.0002 mg/1 <br />Total Recoverable Zinc 0.05 mg/1 <br />m/ - Petal colifora bacteria average concentrations shall be determined by <br />the geometric mean of all samples collected during a thirty (30) <br />cooaecutivn day period. The 7 day average shall be determined by the <br />geometric mean of all samples taken during a seven (7) day period. <br />Code: i - 17 Date: 9-84, revised 10-86, revised 06-87, revised 12-87, <br />revised 12-88 <br />