Laserfiche WebLink
Location of implementation for: <br />GAP OF POLE-TOP GROUND <br />OR PHASE <br />AoanoNu <br />SPncmc <br />a <br />8' Wood <br />CaassnaM <br />NeurWu <br />• Figure 1: Typical Eagle-Safe three-phase pole configuration using a dropped 8-foot <br />crossarm creating a gap between the pole-top ground or phase and the phases on the <br />crossarm. <br />New and/or existing three-phase tangent structures can be framed to provide an additional <br />16 inches of cleazance, bringing the total phase-to-phase sepazation to 60 inches as <br />recommended in Suggested Practices for Raptor Protection on Power Lines: The State <br />of the Art in 1996. This additional clearance required for eagles can be obtained by <br />lowering the crossarm 27 inches on poles with 8-foot crossanns. <br />4.18-5 Revision Date: 2/11/05 <br />Revision No.: MIt-70 <br />