Laserfiche WebLink
CCSV MINING <br /> NEW TRUCK SHOP E.P. 460 SYN <br /> ACUREN FORMAL EXTERNAL INSPECTION 6-2011 <br /> Item Status Comments <br /> 1.0 Tank Containment <br /> 1.1 Containment structure in SMALL CRACKS EXIST IN CONCRETE. <br /> satisfactory condition? ❑ Yes ❑X No* <br /> 1.2 Drainage pipestvalves fit for <br /> continued service ❑Yes ❑ No* X N/A TANK IS INSIDE OF BUILDING. <br /> 2.0 Tank Foundation and Supparts <br /> 2.1 Evidence of tank settlement <br /> or foundation washout? ❑Yes ❑X No* <br /> 2.2 Cracking or spalling of <br /> concrete pad or ring wall? u X Yes u No* N/A SMALL CRACKS EXIST. <br /> 2.3 Tank supports in satisfactory <br /> condition? ❑X Yes ❑No* NIA <br /> 2.4 Water able to drain away from <br /> to nk? ❑ X Yes ❑ No* <br /> 2.5 Grounding strap secured and <br /> In QoDd condition? ❑Yes ❑ No* X NIA <br /> 3.0 Cathodic Protection <br /> 3.1 CID system functional? ❑Yes ❑ No* X N/A <br /> 3.2 Rectifier Reading: ❑Yes ❑ No* X NIA <br /> 4.0 Tank External Coating <br /> 4.1 Evidence of paint failure? ❑ Yes ❑X No' <br /> 5.0 Tank ShelllHeads <br /> 5,1 Noticeable shell/head <br /> distortions, buckling,denting or ❑ Yes ❑X No* <br /> 5.2 Evidence of shellthead <br /> corrosion or cracking? ❑Yes ❑ X No* <br /> 6.0 Tank Manwa s PiRinp and Equipment within Secondary Containment <br /> 6.1 Flanged connection bolls tig t PUMP AND PIPING ON WEST SIDE OF TANK HAS PRODUCT RESIDUE AROUND IT. <br /> and fully engaged with no sign of <br /> wear or oorrosion7 ❑ Yes ❑X No* <br /> 7.0 Tank Roof <br /> 7.1 Stands water on roof? ❑ Yes ❑X No* <br /> 7.2 Evidence of coating cracking, <br /> crazing, peeling, blistering? ❑ Yes ❑X No* <br /> 7.3 Holes in roof? ❑Yes ❑X No* <br />