Laserfiche WebLink
ACUREN <br /> hem Status comments <br /> 8.0 Venting <br /> 8.1 Vents free of obstructions? ❑X Yes ❑ No' PRODUCT RESIDUE EXISTS AROUND VENT BUT IS NOT CLOGGED- <br /> 8-2 Emergency vent operable? <br /> Lift as required? ❑Yes o No' ❑X WA <br /> 9.0 Insulated Tanks <br /> 9.1 Insulation missing? ❑Yes' ❑ No X NIA <br /> 92 Are there noticeable areas of <br /> moisture on the insulation? ❑Yes' ❑ No X NIA <br /> 9.3 Mold on insulation? ❑Yes` ❑ No X NIA <br /> 9.4 Insulation exhibiting damage. ❑Yes` ❑ No X WA <br /> 9.5 Is the insulation sufficiently <br /> protected from water intrusion? ❑Yes ❑No`X NIA <br /> 10.0 Level and Overfill Prevention Instrumentation of Sho -Fabricated Tanks <br /> 10.1 Has the tank liquid level <br /> sensing device been tested to <br /> ensure proper operation? ❑ Yes ❑X No' NIA ELEGTRONIG LEVEL APPEARS TO BE IN GOOD CONDITION VERIFY ACCURACY. <br /> 10.2 Does the tank liquid level <br /> sensing device operate as <br /> required? ❑Yes o No' X N/I <br /> 10.3 Are overfill prevention <br /> devices in proper working <br /> condition? ❑Yes ❑ No' ❑X N/A <br /> 11.0 Electrical Equipment <br /> 11.0 Are tank grounding lines in <br /> good condition? ❑X Yes o No' ❑ N/A <br /> 112 Is electrical wiring for control <br /> boxes/lights in good condition? ❑X Yes ❑ No' o N/A <br /> RECOMMENDATIONS <br /> 1_ REPAIR OR REPLACE FITTING THAT IS LEAKING. <br /> 2_ USE CARE WHEN FILLING TANK SO IT DOES NOT OVERFILL- <br /> 3- COAT/REPAIR CRACKS IN CONCRETE CONTAINMENT AND FOUNDATION. <br /> 4_ PERFORM PERIODIC INSPECTIONS AS OUTLINED IN STI-SPOO1. <br />