i <br /> e <br /> it i,u <br /> /i <br /> Figure 4. 100 gallon dyed diesel day tank within the generator Conex. The large diameter <br /> black pipe in the foreground is the vent pipe that, if installed properly with the top of the <br /> pipe at a height higher than the `elbow' of the return flow line, would ensure return <br /> overflow was directed to the 12,000 gallon diesel tank via the return piping. The vent <br /> pipe had not been reinstalled at the time of the spill. Photo captured Monday, October 21, <br /> 2019. <br /> 10 <br />