Record of Construction Report,VLF2 Recertification Report ■. <br /> ' Subgrade and Geoembrane 9750'-9900'Elevations ■ <br /> Response to DRMS Comments <br /> NewFields Job 475.0106.026 <br /> October 5,2018 <br /> ' The passing extrusion trail seam RCTX-16 is the retest for the failed RCTX-15 test. The welding <br /> machine was adjusted and retested after the failed test. An updated table has been included in <br /> ' this addendum in Attachment 2. <br /> 6. Appendix E.4 Geomembrane Fusion Welding Summary:As mentioned above, the text in <br /> ' section 5.1.5 indicated that destructive samples were to be collected at a rate of 500 <br /> linear feet of seam but this table reflects that was not done, please provide an <br /> explanation as to why. <br /> ' Per the approved technical specification, 02776-0 Geomembrane", Contractor shall test a <br /> pp p , <br /> ' minimum of one destructive test per five hundred (500) feet of seam length..." Based on the <br /> table presented in Appendix E.4, the average distance between each destructive test is <br /> approximately 475'. This results in more tests than the frequency specified in the Technical <br /> Specification. <br /> 7. Appendix E.6 Geomembrane Fusion Destructive Testing Summary:Please describe the <br /> difference between the two columns titled Peel Strength. <br /> During destructive testing of a fusion welded seam, both sides of each of the five test coupons <br /> are tested for Peel Strength. The two columns titled "Peel Strength" on Appendix E.6 <br /> Geomembrane Destructive Testing Summary are used to log the test result values. <br /> ' 8. Appendix E.6 Geomembrane Fusion Destructive Testing Summary: Under the column <br /> titled Shear Strength there are numerous samples that fail the indicated minimum value <br /> of 130 ppi but are marked as passing tests, please explain. If the minimum value shown <br /> is incorrect, please revise the table to reflect the correct value and check the table for <br /> completeness and accuracy(there is a misspelled word in title). <br /> ' Per Table 2.01, Typical Properties, of the approved technical specification, 02776-0 <br /> Geomembrane", the minimum shear strength for a field seams on textured 80 mil LLDPE is 120 <br /> ' ppi, not 130ppi as indicated in the table in Appendix E.6. The table has been corrected and <br /> included in this addendum in Attachment 3. <br /> ' 9. Appendix E.6 Geomembrane Extrusion Destructive Testing Summary: There are two <br /> superscripts shown on the table. <br /> The superscript and notes in the footer on the Table included in Appendix E.7 Geomembrane <br /> Extrusion Destructive Testing Summary, have been removed and the corrected table is included <br /> ' in this addendum in Attachment 4. <br /> 1 <br /> Page 3 <br />