Laserfiche WebLink
POND DEWATERING <br />USE A PUMP WITH A CAPACITY TO DEWATER IN 48 -HOURS <br />POND F <br />---------------- <br />---------------- <br />AS-BUILT WATER VOLUN 3.80 Acre -Feet <br />VOLUME 1237642 Gallons <br />PUMP CAPACITY 430 GPM <br />PUMP SIZE 4" <br />Dewatering Time 2880.00 Minutes <br />48.00 Hours <br />2.00 Days <br />Pump capacity _ 409 gpm with 60' head which includes head loss in pipe. <br />TR -81 App. B-10 10/13 <br />