Laserfiche WebLink
ENERGY (i-- <br /> Trust our People.Trust our Data. i Billings,MT 800.735.4489•Casper,WY 888.235.0515 <br /> ' I College Station,TX 888.690.2218•Gillette,WY 866.686.7175•Helena.MT 877.412.0111 <br /> QA/QC Summary Report <br /> Prepared by Casper,WY Branch <br /> Client: Cotter Corporation Report Date: 02/25/16 <br /> Project: Schwartz- SW 02/09/16 S28676 Work Order: C16020332 <br /> Analyte Count Result Units RL %REC Low Limit High Limit RPD RPDLimit Qual <br /> Method: A4500-F C Analytical Run:MANTECH_160216A <br /> Lab ID: CCV-8644 Continuing Calibration Verification Standard 02/16/16 11.48 <br /> Fluoride 2.04 mg/L 010 102 90 110 <br /> Method: A4500-F C Batch: R209071 <br /> Lab ID: MBLK Method Blank Run: MANTECH_160216A 02/16/16 11:43 <br /> Fluoride ND mg/L 0.09 <br /> Lab ID: LCS-8595 Laboratory Control Sample Run MANTECH_160216A 02/16/16 11.45 <br /> Fluoride 2.00 mg/L 0.10 100 90 110 <br /> Lab ID: C16020331-001AMS Sample Matrix Spike Run MANTECH_160216A 02/16/16 11:54 <br /> Fluoride 2 21 mg/L 0.10 99 80 120 <br /> Lab ID: C16020331-001AMSD Sample Matrix Spike Duplicate Run MANTECH_160216A 02/16/16 11 56 <br /> Fluoride 2.12 mg/L 0.10 95 80 120 4.2 10 <br /> Qualifiers: <br /> RL-Analyte reporting limit. ND-Not detected at the reporting limit. <br /> MDC-Minimum detectable concentration <br /> Page 4 of 17 <br />