Laserfiche WebLink
FIGURES <br />Figure 4.18-2 Typical Eagle -Safe Three -Phase Pole Configuration <br />ADDITIONAL VERTICAL <br />SPACING <br />$" <br />Location of implementation for: <br />GAP OF POLE -TOP GROUND OR <br />PHASE <br />••. <br />NEUTRAL <br />Typical Eagle -Safe three-phase pole configuration using a dropped 8 -foot crossarm creating a gap <br />between the pole -top ground or phase and the phases on the crossarm. <br />New and/or existing three-phase tangent structures can be framed to provide an additional 16 <br />inches of clearance, bringing the total phase -to -phase separation to 60 inches as recommended in <br />Suggested Practices for Raptor Protection on Power Lines: The State of the Art in 1996 This <br />additional clearance required for eagles can be obtained by lowering the crossarm 27 inches on <br />poles with 8 -foot crossarms. <br />Figures 36 Revision Date: 10/06/15 <br />Revision No.: MR -147 <br />