Laserfiche WebLink
<br />002H6 <br /> <br />Durango Pumoing Plant - Stage 1 <br /> <br />c. <br /> <br />Deviations from Specified Lines, Grades, and Dimensions, surface <br />roughness is acceptable. <br /> <br />When roughness height or depth exceeds abrupt tolerance specification, <br />determine roughness slope for comparison to gradual tolerance <br />specification. <br /> <br />1) Measure roughness length and determine roughness slope by <br />dividing roughness height or depth by roughness length (see Figure <br />1). <br /> <br />2) When roughness slope is greater than slope specified by gradual <br />tolerance specification, surface roughness is unacceptable. <br /> <br />3) When roughness slope is less than gradual slope specified and <br />gradual roughness does not cause structure to exceed allowable <br />structural deviations, surface roughness is acceptable. <br /> <br />I: <br />, <br /> <br />1 <br /> <br />Cast-in-Place Concrete <br />03300 - 42 <br />