Laserfiche WebLink
<br />002443 <br />, <br /> <br />. Durango Pumoing Plant - Stage I <br /> <br />Table 03300E - Deviations from Specified Lines, Grades, and Dimensions <br /> <br />A. PUMPING PLANT STRUCTURES AND OTHER STRUCTURES <br />1. Footings: <br />(a) Variation in length and width dimensions <br />from those specified -1/2 inch <br /> +2 inches <br />(b) Horizontal misplacement or eccentricity: <br />(1) 2 percent of footing width in 2 inches <br />direction of misplacement, but not more than <br /> 5 percent of <br />(c) Reduction in thickness specified thickness <br />2. Variation of horizontal dimensions at all floor and rooflevels <br />from specified position in plan: <br />(a) Overall building dimensions '" 1/2 inch per <br /> 1 00- foot length <br /> with maximum for <br /> entire length of", I <br /> inch <br />(b) Overall bay dimensions as limited by '" 3/8 inch <br />2( c )below but not to exceed <br />(c) Intermediate dimensions for column, wall, <br />and partition locations: <br />(I) For dimensions less than 10 feet '" 1/4 inch <br />(2) For dimensions equal to or greater than <br />I 0 feet but less than 20 feet '" 3/8 inch <br />(3) For dimensions 20 feet or more j; 1/2 inch <br /> <br />Cast-in-Place Concrete <br />03300-36 <br />