Laserfiche WebLink
<br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I 2) <br />I 3) <br />4) <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br /> <br /> Table 4.5 <br /> Mini.um Supply Rate and Storage Requirements <br /> Minillllm Volume <br /> Daily2 Supply Required Fire Flowl Peak Hour Consumption3 at Supply Minimum <br /> Production Rate l!l 20 Rate for Storage <br /> Max Week Hrs/Day Rate Duration Volume Rate Duration Volume 4 Hr FF Required <br />Year Gallons GPM GPM Hours Gallons GPM Hours Gallons Gallons Gallons <br />1986 658,080 548 500 4 120,000 959 4 230,160 131,520 218,640 <br />1996 685,440 571 500 4 120,000 999 4 239,760 137 ,040 222,720 <br />2006 711 ,360 593 500 4 120,000 1,038 4 249,120 142,320 226,800 <br />2016 789,120 658 500 4 120,000 1,152 4 276,480 157,920 238,560 <br />2026 943,200 786 500 4 120,000 1,376 4 330,240 188,640 261,600 <br /> <br />Notes: <br />1) Based on ISO minimum fire/flow requirements and on capacity of existing distribution <br />lines. Fire flows for this system have never been guaranteed due to a combination of <br />storage, distribution and fire fighting equipment deficiencies. <br /> <br />Max week assumed to be 2X average week. See Table 4.2 for July values. <br /> <br />Peak hour consumption based on 1.75X daily production at max week. <br />Existing storage capacity is 250,000 gallons at Bull Hill storage tank. <br /> <br />26 <br />