Laserfiche WebLink
Animas -La Plata Project <br />Feb 13, 2013 Draft Transfer Inspection Report <br />e. 480 Volt Motor Control Centers <br />Two motor control centers designated MCA and MCB are rated 480 volt, 3- phase. <br />The motor control centers provide the motor starters and controls for all motor - <br />operated butterfly valves and the main unit cooling water pumps. Feeder breakers <br />provide power for 480 volt power receptacles in the main pump bay. <br />Auxiliary Control Panel <br />The auxiliary control panel is designated CCA and is located at the south end of the <br />motor control gallery. The control panel provides electrical interlocks for operation <br />of the main pumping units. The control panel also provides status and alarm <br />indicating lights for the pumping plant auxiliary systems. Electrical controls <br />associated with filling and draining are also provided at CCA and require input from <br />the following motor - operated fill and drain valves: <br />• MPA -Unit 1 City of Durango isolation discharge valve <br />• MPB -Unit 2 City of Durango isolation discharge valve <br />• MPC - Ridges Basin discharge manifold isolation discharge valve <br />• MPD -City of Durango discharge manifold isolation discharge valve <br />• MPE -Unit 1 isolation filling valve <br />• MPF -Unit 2 isolation filling valve <br />• MPG -Drain line discharge valve <br />• M1F -Unit 1 guard valve <br />• M2F -Unit 2 guard valve <br />A programmable logic controller (PLC) and a graphic operator terminal are used to <br />implement the control logic and to provide a single point of operation for the <br />pumping plant motor - operated fill and drain valves. <br />TRANSFER ISSUE <br />STIPULATION <br />Operation logic does not <br />Reclamation will Identify the differences between the DOC and <br />match Designer's Operating <br />Motor Control Gallery, El. 6447.17 <br />CSA <br />actual PLC functionality, and revise as necessary. <br />Criteria document <br />CSB <br />Labels conflict with DOC <br />Reclamation with match labels on the ACP to the naming in the <br />and SOP <br />SOP <br />g. Motor Control Board <br />Individual motor control boards are provided to operate /monitor the following <br />pumping plant auxiliary equipment: <br />Name <br />Equipment <br />Location <br />CCA <br />Auxiliary Control Panel <br />Motor Control Gallery, El. 6447.17 <br />CSA <br />Mechanical Seal Water Disconnect <br />Service Bay, El. 6418.00 <br />CSB <br />Mechanical Seal Water Control <br />CSC <br />Plant Drainage Sump Pump <br />Service Bay, El. 6418.00 <br />CSD <br />Plant Sump Pumps <br />Service Bay, El. 6432.58 <br />CHA <br />Fish Screen Cleaner <br />Intake Structure Control Building <br />Transferred Works Inspection 24 Animas -La Plata Project <br />